6.2 TRACING SCHEME WHEN RED LAMP LIT
Use caution when fault tracing on Travel Power. Please observe that
this is a 230 V installation.
Red LED is lit YES Have several connec-
tions and disconnect-
ions of large loads
within a short interval
occurred?
YES Turn off the engine for 1 minute and
then restart the Travel Power without
load. Avoid such behavior in the
future.
NO
Has a large motor or
compressor load been
connected?
YES Reduce the load and avoid starting
large motors/compressors at the
same time
Restart Travel
Power with the
on-off switch
NO
Is there a lose
connection in the
230 V installation or in
the generator wiring?
YES Check the wiring Restart Travel
Power with the
on-off switch
NO
Is a three-position
switching device
installed?
YES Check according to section 3.6 Restart Travel
Power with the
on-off switch
NO
Are there reasons to
suspect that the
temperature protection
has been triggered?
YES Check with section 3.2 that the
power box installation is OK and
make sure that the ventilation
openings are unobstructed and that
the ambient temperature is normal
Restart Travel
Power with the
on-off switch